- Strong deep profile aluminum cruciform pedestal heat to maintain
lateral stability of panels.
- ( Optional antivibration pads available )
- Unique feathered perimeter to arrest heavy point load deflection
- Quadrants to accept box section stringers. For RFI Shielding,
Stringers are bonded electrically and mechanically to pedestal head
- Computer equipment can be earthed or bonded to stringer.
|
- 16mm stud for cavities 68mm to 250mm, adjustments 30mm. Galvanized base plate 100mm sq.
- 27mm tube for cavities 140mm to 1200mm, adjustments 60mm. Galvanized base plate 100mm sq.
- 38mm tube for cavities 170mm to 1800mm, adjustments 60mm. Aluminum base plate 130mm dia.
- 50mm tube for cavities 140mm to 2400mm, adjustments 60mm. Steel base
plate 140mm sq.
|
The RFI Floor Shielding
System is engineered to suit all loading requirements for
offices from a uniformly distributed load of 5 kN/m2 to extra
heavy uniformly distributed loads of 36 kN/m2.
Vertical
Load:
27mm diameter pedestals are designed and engineered to withstand
in excess of 25 kN vertical load.
|