Head..
  • Strong deep profiled aluminum cruciform pedestal head to maintain lateral stability of panels (optional anti-vibration pads available).
  • Unique feathered perimeter to arrest heavy point load deflection.
  • Quadrants to accept clip on 'U' channel or box section strings. For increased strength or RFI Shielding.

Stem, Base & Floor Heights..
  • 16mm stud for cavities 68mm to 250mm adjustment 30mm.
  • Galvanized base plate 100mm sq.
  • 27mm tube for cavities 140mm to 1200mm adjustments 60mm.
  • Galvanized base plate 100mm sq.
  • 38mm tube for cavities 170mm to 1800mm adjustments 60mm.
  • Aluminum base plate 130mm sq.
  • 50mm tube for cavities 140mm to 2400mm adjustments 60mm.
  • Steel base plate 140mm sq.
    Please specify required height.

    Floor Loads

    The Triple 'R' System is engineered to suit all loading requirements for offices from a uniformly distributed load of 5 kN/m2 extra heavy uniformly distributed loads of 36kN/m2

    Vertical load: 27mm diameter pedestals are designed and engineered to withstand in excess of 25kN vertical load.

    Specify Triple 'R'
    Panel Construction:

    600x 600mm steel encapsulation panels, thickness designed and engineered to suit uniformly distributed loading.

    From 5kN/m2 to 36kN/m2 (please specify your UDL requirement).

    The panel to have triple rolled reinforced side edged to give added strength and durability.

    The steel lid to have down-turned edged rolled and overlapping the steel tray by a minimum of 9mm and to be turned in at an angle of 45oto prevent delamination.

    Pedestal construction:

    Solid steel or heavy tube swaged to galvanized base plate with, and including, 130mm diameter x 6mm thick LM24 aluminum head.

    Comprised 62mm long x 6mm wide x 13mm deep cruciform for maximum lateral stability to positively lock panels in positive to prevent movement without the need for screwing panels to the pedestal heads.

    The pedestal head to be feathered at perimeter to arrest heavy point load deflection